Oct 12, 2023
Tso lus
1. What is charging protection?
When the circuit breaker where the device is located is used to charge components such as the busbar and is connected to a faulty component, there is charging protection as a protection in this situation. The charging protection consists of two sections of two-time phase overcurrent and one section of zero-sequence overcurrent composed of phases. The current is taken from the TA of this circuit breaker.
2. What is dead zone protection?
A brief explanation of the dead zone: The following fault at K1 is within the I bus protection zone, but after the I bus protection action trips all I bus circuit breakers including 1DL, the fault point is still in the system. This type of fault is a dead zone fault. .
Action of dead zone protection: three-phase trip signal (for example: three tripping of transformer, three tripping of line, or three split-phase tripping of A, B and C at the same time) + three-phase trip (TWJ signal) + dead zone current action , the dead zone protection is started after the dead zone delay.
